|
Typical Specifications for Horizontal Fire
Pumps
General:
The pump manufacturer shall
supply the pumps furnished for fire protection service with specific
drivers, controls and pump accessory items. The pump and control
shall be:
Underwriters Laboratories (UL) Listed
Factory Mutual Research Corporation (FM) Approved.
UL Listed and FM Approved.
Underwriters Laboratories-Canada (ULC) Listed.
For fire protection service.
The pumping equipment shall be installed as recommended in the
National Fire Protection Association NFPA Pamphlet 20, standard for
the installation of centrifugal Fire Pumps. The fire pump shall be
designed to delver U.S. gallons per minute. (Gpm) at a total
deferential pressure of
psi. The fire pump shall also be capable of delivering not less that
150% of rated flow at not less than 65% rated head. Peerless Pump
model shall be furnished with drive, control and accessories as
detailed in this specification. (Consult Peerless pump selection
tables. B-1510). Pump manufacturer shall have unit responsibility
for the proper operation of the complete unit assembly as indicated
by field acceptance tests.

Manufacturer’s Factory Tests:
Each individual pump shall be
hydrostatically tested prior to shipment. The pump shall be
hydrostatically tested at a pressure of not less than one and
one-half times the no flow shout off) head of the pumps maximum
diameter impeller plus the maximum allowable suction head, but in no
case less than 250 psig.
FIELD
ACCEPTANCE TEST:
A field acceptance performance
test shall be conduced upon competition of pump installation. The
test shall be made by flowing water through calibrated nozzles.
Approved flow meters or other such accurate devices as may be
selected by the authority have jurisdiction. The test shell be
conducted as recommended in NFPA pamphlet 20 by
The installing contractor
The owner
The owner’s representative
(Other)
In the presence of the
authority having jurisdiction and with that authority's final
approval and acceptance. Failure to submit documentation of factory
and field tests will be just cause for equipment rejection.
Horizontal Centrifugal Pumps:
The fire pump shall be of
horizontal centrifugal (single stage) (multistage) construction
specifically labeled for fire service and shall be a Peerless Pump
model. The pump shall be connected to the (fire standpipe) (fire
sprinkler) (underground fire main) system the suction supply for the
fire pump shall be from a (public service water main) elevated
storage tank) (ground storage tank) underground reservoir) at a
maximum pressure of pounds per square inch (psi) and a minimum
pressure of psi. The pump
casing shall ha cast iron with inch (125) pound rating suction end
inch (125) (250) pound rating discharge flanges machined to American
National standards Institute (ANSI) dimensions.
Electric Motors:
The pump driver shall be horizontal foot mounted ball bearing
induction motor rated horsepower, 3 phases, 60 Hertz with open
drip-proof NEMA enclosure for operation on volt service. The motor
locked rotor current shall not exceed the values stated in NFPA
Pamphlet 20. The motor shall be mounted on a steel base common to
the pump and shall be connected to the pump with a flexible coupling
protected by a suitable guard. The fire pump manufacturer shall
accurately align the pump and motor shafts prior to shipment. After
field installation but prior to grouting the base, a millwright or
similarly qualified person shall check and verity or correct the
shaft alignment.
Electric Motor Controllers:
The automatic electric motor controller shall be UL listed and FM
approved specifically for fire pump service. The controller hall be
designed for
Across-the-line
Part winding
Primary resistance reduced voltage
Wye Delta Open Transition
Wye
Delta Closed transition
Auto-transformer
type starting.
The controller shall be
rated for the horsepower specified in this specification Electric
Motors suction. The controller shall be capable of interrupting a
short circuit current at least equal to the available short circuit
current in the controller supply circuit. This fire pump controller
installation requires an interrupting capacity of not less than
amps RMS symmetrical at an operating voltage of volts.
The controller shall be
Floor or wall mounted for electrical connection to the motor by the
equipment installer.
Mounted on a common base
with the fire pump and wired to the motor by the pump manufacturer.
Fittings:
The pump manufacturer shall
furnish piping accessory items for the pump installation, which will
adapt the pump connections to the fire protection system and test
connection as follows. Fittings subjected to pump discharge pressure
shall be ANSI (125) (250) pound rating Fittings subjected to suction
pressure shall be ANSI 125 pound rating.
Eccentric tapered suction reducer
Concentric tapered discharge increaser
Hose valve test head
Hose valves with caps and chains
Pump casing relief valve
Automatic air release valve
Ball drip valve
Suction and
discharge pressure gauges
Additional accessories
required when pump is engine or steam turbine driven:
Main relief valve
Direct acting (spring actuated)
Pilot operated (hydraulically actuated)
Relief valve overflow cone enclosed type
Discharge tee with elbow (or mounting relief valve)
DIESEL ENGINES:
The pump driver shall be a
horizontal shaft type internal combustion engine Model manufactured
by, rated at rpm, clockwise rotation viewed from the end opposite
the pump. The pump manufacturer with, at a minimum, shall provide
the engine the following accessories for automatic operation
Mantrol UL listed emergency manual operator, factory wired and
mounted on the engine junction box for standby engine starting and
operation incase of main controller or interconnecting wiring
malfunction.
Cooling waterlines pressure regulator. Strainer, bypass lines and
necessary fittings for engine cooling systems, prepiped and factory
mounted.
Flexible exhaust connector
Exhaust silencer
Engine jacket water heater, factory installed.
One set dual batteries, lead acid storage type.
Fuel system as recommended in NFPA Pamphlet 20
Fuel storage tank sized to provide a minimum supply of one gallon of
fuel per engine maximum rated horsepower plus 5% for sump area
plus 5% to expansion area. The tank shall be furnished with legs far
floor mounting and with a direct reading level gauge.
The pump manufacturer prior to shipment shall run
the engine tested with the pump.
ENGINE CONTROLLERS:
The automatic engine
controller shall be UL listed and FM approved specifically for fire
pump service.
The controller must be
capable of performing or contain the following features:
Built in battery charger
Time clock for weekly automatic test
System pressure recorder
Timing relay for automatic stop
Power failure start
Low fuel level switch
Pump room alarm audible and visual signals
The controller shall be wired to the corresponding engine function
terminals and shall be mounted on common base with the engine and
pump. A complete running test of the base mounted controller, the
pump manufacturer prior to shipment shall perform engine and pump.
The engine
controller shall be floor mounted for electrical connection to the
engine by the equipment installer.
 |
|
Typical Specifications for Vertical
Turbine Fire Pumps
GENERAL:
the pump manufacturer
shall supply the pumps furnished for fire protection service
with the specified drivers, controls and pump accessory items.
The ump, driver and control shall be:
Underwriters Laboratories (UL) Listed
Factory Mutual Research Corporation
(FM) Approved
UL Listed and FM Approved
Underwriters Laboratories-Canada (ULC)
listed for fire protection service.
The pumping equipment
shall be installed as recommended in the National Fire
Protection Association (NFPA) Pamphlet 20. Standard for the
Installation of Centrifugal Fire Pumps. The fire pump shall be
designed to deliver U.S. gallons per minute (gpm) at a total
differential pressure of psi. The fire pump shall also be
capable of delivering not less than 150% of rated flow at not
less than 65% rated head. Peerless Pump model shall be furnished
with drive, controls and accessories as detailed in this
specification. (Consult Peerless Pump selection tables,
B-1510). Pump manufacturer shall have unit responsibility for
the proper operation of the complete unit assembly as indicated
by field acceptance tests.
MANUFACTURER’S FACTORY
TESTS:
Each individual pump
shall be run tested prior to shipment. Vertical turbine bowl and
discharge head assemblies shall be hydrostatically tested at a
pressure not less than one and one-half tines the no flow
(shutoff) head of the pump's maximum diameter impeller but in no
case less than 250 psig.
FIELD ACCEPTANCE TEST:
A field acceptance
performance test shall be conducted upon completion of pump
installation. The test shall be made by flowing water through
calibrated nozzles, the authority having jurisdiction may
select approved flow meters or other such accurate devices as
the test shall be conducted as recommended in NFPA Pamphlet 20
by
The installing contractor
The owner
The owner's representative
(Other)
In the presence of the
authority having jurisdiction and with that authority's final
approval and acceptance. Failure to submit documentation of
factory and field tests will be just cause for equipment
rejection.
VERTICAL TURBINE PUMPS:
The fire pump shall be a
Peerless model vertical shaft turbine pump. The pump shall be
specifically labeled for fire service (under-ground fire main)
system. The water supply for the fire pump shall be from
A water well of style, dimension and
water productivity as recommended in NFPA 20.
A sump or equivalent intake structure
of style, dimension and water capacity as recommended in NFPA
Pamphlet 20.
The total installed length
of the pump from bottom of base plate to bottom of suction
inlet manifold shall be feet. The pump discharge head assembly
shall be cast iron and fitted with a inch discharge connection
machined to American National Standards Institute (ANSI)
125 pound rating dimensions
250 pound rating dimensions
The pump discharge head
shall provide rigid mounting support for the complete pump
assembly and for the:
Vertical hollow shaft motor
(electric motor driven pumps)
Right angle gear drive (diesel
engine driven pumps)
The pump line shaft
bearings shall be
Water lubricated by the liquid being
pumped (for static water levels up to 50 feet)
Oil lubricated with bronze bearings
contained in enclosing tubing (for static water levels 51
feet and greater)
Pump column pipe (and oil
tube when applicable) shall be in sections not longer than 10
feet each. Pump bowl assemblies shall include cast iron enameled
bowls, cast bronze impellers and bowl lateral seal rings. Pump
bowl assemblies shall be submerged as recommended in NFPA
Pamphlet 20. Each pump shall be installed with a cast or
fabricated nonferrous metal strainer having a free area of not
less than four times the suction inlet area, Strainer openings
shall be sized to restrict the passage of objects one-half inch
sphere size.
ELECTRIC
MOTORS:
The pump driver shall be a
vertical hollow shaft induction motor
Rated horsepower, 3
phase, 60 Hertz, with Weather Protected Type 1 NEMA enclosure
for operation on volt service. The motor locked rotor current
shall not exceed the values stated in NFPA Pamphlet 20. The
motor shall be constructed so that the total hydraulic and
static thrust of the pump's rotating assembly can be carried by
the motor thrust bearing (s). The motor shall mount directly on
the pump discharge head assembly with a registered fit for
correct shaft alignment. The motor shall be equipped with a top
drive coupling and nut for axial adjustment of the pump
impellers and shall have a non-reverse ratchet to prevent pump
backspin.
ELECTRIC MOTOR
CONTROLLERS:
The automatic electric
motor controller shall be UL listed and FM approved specifically
for fire pump service. The controller shall be designed for:
Across-the-line
Part winding
Primary resistance reduced voltage
Wye Delta Open Transition
Wye Delta Closed Transition
Autotransformer type starting.
The controller shall be
rated for the horsepower specified in this specification
Electric Motors section. The controller shall be capable of
interrupting a short circuit current at least equal to the
available short circuit current in the controller supply
circuit. This fire pump controller installation requires an
interrupting capacity rating of not less than amps RMS
symmetrical at an operating voltage of volts.
The controller shall be
Floor or wall mounted for electrical
connection to the motor by the equipment installer.
Mounted on a common base with the
fire pump and wired to the motor by the pump manufacturer.
FITTINGS:
The pump manufacturer
shall furnish piping accessory items for the pump installation,
which will adapt the pump connections to the fire protection
system and test connection as follows. Fire pump fittings, which
are subjected to pump discharge pressure, shall be ANSI (125)
(250) pound rating.
Hose valve test head
Hose valves with caps and chains
Ball drip valve
Automatic air release valve
Discharge pressure gauge
Water level gauge device
Additional accessories
required when pump is engine or steam turbine driven:
Main relief valve,
Direct acting (spring actuated)
Pilot operated
(hydraulically actuated)
Relief valve overflow cone, enclosed
type
Discharge tee with elbow
(for mounting relief valve)
GEAR
DRIVES:
Engine driven vertical
turbine pumps shall be furnished with a vertical hollow shaft
right angle gear. The drive shall be direct connected to the
pump shaft and be equipped with a non-reverse ratchet. The drive
shall be connected to the engine by an approved flex shaft with
an enclosing guard as recommended in NFPA Pamphlet 20. The drive
shall have provision for adjusting the pump impeller lateral
setting for proper pump operation and performance.
DIESEL ENGINES:
The pump driver
shall be a horizontal shaft type internal combustion engine
Model manufactured by ,
rated at rpm, clockwise rotation viewed from the end opposite the pump. The
pump manufacturer with, at a minimum, shall provide the engine
the following accessories for automatic operation.
Mantrol UL listed emergency manual
operator, factory wired and mounted on the engine junction box
for standby engine starting and operation in case of main
controller or interconnecting wiring malfunction.
Cooling waterlines, pressure
regulator, strainer, bypass lines and necessary fittings for
engine cooling system. Pre-piped and factory mounted,
Flexible exhaust connector
Residential exhaust silencer
Engine jacket water heater, factory
installed.
One set dual batteries, lead acid
storage type.
Fuel system as recommended in NFPA
Pamphlet 20
Fuel storage tank sized to provide a
minimum supply of one gallon of fuel per engine maximum rated
horsepower plus 50/0 for sump area plus 5% for expansion area.
The tank shall be furnished with legs for floor mounting and
with a direct reading level gauge.
ENGINE CONTROLLERS:
The automatic engine
controller shall be UL listed and FM approved specifically for
fire pump service. The controller must be capable of performing
or contain the following features:
Built in battery charger
Time clock for weekly automatic test
System pressure recorder
Timing relay for automatic stop
Power failure start
Low fuel level switch
Pump room alarm audible and visual
signals
The controller shall be wired to the
corresponding engine function terminals and shall be mounted on
a common base with the engine. An engine / controller check test
shall be performed by the pump manufacturer for proper engine
and controller operation.
The engine controller shall be floor
mounted for electrical connection to the engine by the equipment
installer.

|
Typical Specifications for Vertical
In-Line Fire Pumps
GENERAL:
The pump manufacturer
shall supply the pumps furnished for fire protection service
with the specified drivers, controls and pump accessory items.
The pump, driver and control shall be
Underwriters Laboratories
(UL) Listed
Underwriters Laboratories-Canada (ULC)
listed for fire protection service.
The pumping equipment
shall be installed as recommended in the National Fire
Protection Association (NFPA) Pamphlet 20, Standard for the
Installation of Centrifugal Fire Pumps. The fire pump shall be
designed to deliver U.S. gallons per minute (gpm) at a total
differential pressure of
psi. The fire pump shall also be capable of delivering
not less than 150% of rated flow at not less than 65% rated
head. Peerless Pump model shall be furnished with drive,
controls and accessories as detailed in this specification.
(Consult Peerless Pump selection tables, B-1510). Pump
manufacturer shall have unit responsibility for the proper
operation of the complete unit assembly as indicated by field
acceptance tests.
MANUFACTURER'S FACTORY TESTS:
Each individual pump
shall be hydrostatically tested and run tested prior to
shipment. The pump shall be hydrostatically tested at a pressure
of not less than one and one-half times the no flow (shut off)
head of the pump's maximum diameter impeller plus the maximum
allowable suction head but in no case less than 250 psig.
FIELD ACCEPTANCE TEST:
A field acceptance
performance test shall be conducted upon completion of pump
installation. The test shall be made by flowing water through
calibrated nozzles, the authority having jurisdiction may
select approved flow meters or other such accurate devices as
the test shall be conducted as recommended in NFPA Pamphlet 20
by
The
installing contractor
The
owner
The
owner's representative
(Other)
In the presence of the
authority having jurisdiction and with that authority's final
approval and acceptance. Failure to submit documentation of
factory and field tests will be just cause for equipment
rejection.
VERTICAL IN-LINE CENTRIFUGAL PUMPS:
The fire pump shall be a
Peerless model PVF vertical in-line fire pump. The suction and
discharge flanges shall be of identical dimensions and shall be
displaced 180° with centerlines concentric on the same
horizontal plane. The pump shall be specifically labeled for
fire service and shall be connected to the (fire standpipe)
(fire sprinkler) (underground fire main) system. The suction
supply for the fire pump shall be from a (public service water
main) (elevated storage tank) (ground storage tank) (underground
reservoir) at a maximum pressure of pounds per square inch (psi)
and a minimum pressure of psi. The pump casing shall be cast
iron with inch 125 pound rating suction and inch (125) (250)
pound rating discharge flanges machined to American National
Standards Institute (ANSI) dimensions.
SHAFT SEALING SHALL BE ACCOMPLISHED BY:
(UL, ULC) At least five rings of a
suitable no asbestos packing. The stuffing box shall be equipped
with a lantern ring with water supplied to the stuffing box by a
tap line connected to the discharge side of the pump.
(ULC only) A face type mechanical
seal with Ni-resist stationary seat, carbon washer, ethylene
propylene flexible members, brass metal parts and 18-8
stainless steel spring. Seal shall be mounted over a bronze
shaft sleeve.
ELECTRIC MOTORS:
The pump driver shall be
an H.I./NEMA JM/JP frame, ODP induction motor close coupled to
the driven pump. The motor shall be rated horsepower, 3 phases,
60 Hertz with open drip-proof NEMA enclosure for operation on
volt service. The motor locked rotor current shall not exceed
the values stated in NFPA Pamphlet 20.
ELECTRIC MOTOR CONTROLLERS:
The automatic electric
motor controller shall be UL listed and FM approved specifically
for fire pump service. The controller shall be designed for
Limited service
Across-the-line.
Part winding
Primary resistance reduced voltage
Wye Delta Open Transition
Wye Delta Closed Transition
Autotransformer type starting.
The controller shall be
rated for the horsepower specified in this specification
Electric Motors section. The controller shall be capable of
interrupting a short circuit current at least equal to the
available short circuit current in the controller supply
circuit. This fire pump controller installation requires an
interrupting capacity rating of not less than amps RMS
symmetrical at an operating voltage of volts. The controller
shall be floor or wall mounted for electrical connection to the
motor by the equipment installer.
FITTINGS:
The pump manufacturer shall furnish piping accessory items for
the pump installation, which will adapt the pump connections to
the fire protection system and test connection as follows.
Fittings subjected to pump discharge pressure shall be ANSI
(125) (250) pound rating. Fittings subjected to suction
pressure shall be ANSI 125 pound rating.
Eccentric tapered suction
reducer
Concentric tapered discharge increaser
Hose valve test head
Hose valves with caps and chains
Pump casing relief valve
Automatic air release valve
Drain valve
Suction and discharge
pressure gauges
 |
|
|